FieldServer FS-8700-84 User Manual

Page 21

Advertising
background image

FS-8700-84_Lutron_eLumen Driver Manual

Page 18 of 36


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.1.19.

System Control Commands containing no Parameters: – Select System Scene(s)

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Sel_scene,

Lut_triggers,

2,

awt,

LUT_GRF6_0,

sel_scene,

Scene_list,

0,

1


DA_Lut_List data setup
Position from DA_Lut_List_Offset

Description

0-63

System scenes to select

4.1.20.

System Control Commands containing no Parameters: – Disable Timeclock until Enabled

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Dis_tck_u_e,

Lut_triggers,

3,

awt,

LUT_GRF6_0,

dis_tclk_u_e,

Area_list,

0,

1


DA_Lut_List data setup
Position from DA_Lut_List_Offset

Description

0-31

Area timeclocks to disable

4.1.21.

System Control Commands containing no Parameters: – Disable timeclock until end of day or

enable issued

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Dis_tck_u_eodoe,

Lut_triggers,

4,

awt,

LUT_GRF6_0,

dis_tclk_u_eodoe,

Area_list,

0,

1


DA_Lut_List data setup
Position from DA_Lut_List_Offset

Description

0-31

Area timeclocks to disable