FieldServer FS-8700-84 User Manual
Page 9

FS-8700-84_Lutron_eLumen Driver Manual
Page 6 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]
1.04
Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the
device is connected to the
FieldServer
P1-P8, R1-R2
1
Protocol
Specify protocol used
eLumen
Baud*
Specify baud rate
9600 – Vendor limitation
Parity* Specify
parity None
Data_Bits*
Specify data bits
8
Stop_Bits*
Specify stop bits
1
Handshaking*
Specify hardware
handshaking
None
Poll _Delay*
Time between internal polls 0-32000 seconds, 1 second
Example
// Client Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Data Bits,
Stop Bits,
Poll_Delay
P1,
eLumen,
9600,
None,
None,
1,
0.100s
1.05
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric
characters
Node_ID
The eLumen processor
address - only decimal values
allowed e.g. 11 hex has to be
entered as 17.
0-255
Protocol
Specify protocol used
eLumen
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
1
Node_type
Specifies the eLumen
command and data format
Hex, decimal
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for
details of the ports available on specific hardware.