FieldServer FS-8700-84 User Manual
Page 26

FS-8700-84_Lutron_eLumen Driver Manual
Page 23 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]
4.1.29.
System Control Commands containing no Parameters: Timeclock new schedule
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
DA_Lut_List,
DA_Lut_List_Offset,
Length
Tck_new_sched,
Lut_triggers,
12,
awt,
LUT_GRF6_0,
tclk_new_schedule,
Clk_sched,
0,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
Area tclk 0
1 Schedule
0
2
Area tclk 1
3 Schedule
1
.. ..
60
Area tclk 30
61 Schedule
30
62
Area tclk 31
63 Schedule
31
Note: 1 to 32 new schedules may be started by this command. To trigger this command, write the number of area timeclocks into the Data Array
specified by Data_Array_Name at Data_Array_Offset.
4.1.30.
System Control Commands containing no Parameters: Set timeclock
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
DA_Lut_List,
DA_Lut_List_Offset,
Length
Set_tck,
Lut_triggers,
13,
awt,
LUT_GRF6_0,
set_tclk,
Set_tclk,
0,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
Hour ( 0-23 )
1
Minutes ( 0-59 )
2
Month ( 1-12 )
3
Day of month ( 1-31 )
4
Year ( 0 – 99 )
5