4.1.29.

System Control Commands containing no Parameters: Timeclock new schedule

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Tck_new_sched,

Lut_triggers,

12,

awt,

LUT_GRF6_0,

tclk_new_schedule,

Clk_sched,

0,

1


DA_Lut_List data setup
Position from DA_Lut_List_Offset

Description

0

Area tclk 0

1 Schedule

0

2

Area tclk 1

3 Schedule

1

.. ..
60

Area tclk 30

61 Schedule

30

62

Area tclk 31

63 Schedule

31


Note: 1 to 32 new schedules may be started by this command. To trigger this command, write the number of area timeclocks into the Data Array
specified by Data_Array_Name at Data_Array_Offset.

4.1.30.

System Control Commands containing no Parameters: Set timeclock

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Set_tck,

Lut_triggers,

13,

awt,

LUT_GRF6_0,

set_tclk,

Set_tclk,

0,

1


DA_Lut_List data setup
Position from DA_Lut_List_Offset

Description

0

Hour ( 0-23 )

1

Minutes ( 0-59 )

2

Month ( 1-12 )

3

Day of month ( 1-31 )

4

Year ( 0 – 99 )

5

Day of week ( 1-7, 1=Sunday )