4.1.11.

System Monitor Command – Timeclock Status

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Scan_Interval,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

Area,

Length

Tclk_sts_00,

1s,

Tclk_status,

0,

rdbc,

LUT_GRF6_0,

timeclock_status,

0,

4

Tclk_sts_01,

1s,

Tclk_status,

4,

rdbc,

LUT_GRF6_0,

timeclock_status,

1,

4


Data storage in Data Array
Position from offset

Description

0 Schedule

number

1

Next event type (1 = no more events, 2 = timeclock disabled, 3 = astronomic event, 4 = realtime event )

2

Next event time ( minutes past midnight )

3 Next

script


Note: This command stores 4 data values. To prevent overlaps, remember to increment Data_Array_Offset by 4 when referencing the same Data
Array with other Map Descriptors.

4.1.12.

System Monitor Command – Zone Intensity

// Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

Scan_Interval,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

Zone,

Length

Zn_int_00,

1s,

Zone_int,

0,

rdbc,

LUT_GRF6_0,

zone_intensity,

0,

1

Zn_int_01,

1s,

Zone_int,

1,

rdbc,

LUT_GRF6_0,

zone_intensity,

1,

1


Data storage in Data Array
Position from offset

Description

0

Zone intensity ( 0-127 )


Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data