4.1.11.
System Monitor Command – Timeclock Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Scan_Interval,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
Area,
Length
Tclk_sts_00,
1s,
Tclk_status,
0,
rdbc,
LUT_GRF6_0,
timeclock_status,
0,
4
Tclk_sts_01,
1s,
Tclk_status,
4,
rdbc,
LUT_GRF6_0,
timeclock_status,
1,
4
Data storage in Data Array
Position from offset
Description
0 Schedule
number
1
Next event type (1 = no more events, 2 = timeclock disabled, 3 = astronomic event, 4 = realtime event )
2
Next event time ( minutes past midnight )
3 Next
script
Note: This command stores 4 data values. To prevent overlaps, remember to increment Data_Array_Offset by 4 when referencing the same Data
Array with other Map Descriptors.
4.1.12.
System Monitor Command – Zone Intensity
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Scan_Interval,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
Zone,
Length
Zn_int_00,
1s,
Zone_int,
0,
rdbc,
LUT_GRF6_0,
zone_intensity,
0,
1
Zn_int_01,
1s,
Zone_int,
1,
rdbc,
LUT_GRF6_0,
zone_intensity,
1,
1
Data storage in Data Array
Position from offset
Description
0
Zone intensity ( 0-127 )
Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data