MLDV Series Gas Fireplace

*3”

**1”

**1”

**1”

**1”

*3”

fP1990

vent pipe clearances

VENTING INSTALLATION

Figure 10 -
Combustible Clearances for Vent Pipe

* A minimum of 3" clearance to the top is required
along horizontal length until flue pipe penetrates
outside wall.
** A minimum 1" clearance to combustibles permitted
all around flue at outside wall

This fireplace must be vented to the
outside. The venting system must NEVER
be attached to a chimney serving a separate
solid fuel burning appliance. Each gas
appliance must use a separate vent system.
Do not use common vent systems.

Horizontal sections of this vent system
require a minimum of 3” clearances to
combustibles at the top of the flue and 1”
clearance at the sides and bottom until
the flue penetrates the outside wall. A
minimum 1” clearance all around the flue
is acceptable at this point of penetration. If
vertical rise is 7
Z\x” feet or higher when top
venting, the clearance to combustibles is
1” on all sides of the horizontal run.
Vertical sections of this vent system require
a minimum of 1” clearance to combustibles
on all sides of the pipe.