Mldv series gas fireplace, Flex vent installation, Fp1975 pipe connection – Monessen Hearth DIRECT VENT MLDV500 User Manual

Page 27: Fp1976 horizontal flex

Advertising
background image

75D0004

7

MLDV Series Gas Fireplace

FLEx VENT INSTALLATION

1. Always maintain the required clearance when routing the flex vent assembly.
. Install firestop spacers, Figure 38, when penetrating ceiling, attic spaces, or walls.
3. Do not allow the flexible vent to bend in radius tighter than 5" (17 mm). Figure 37
4. Horizontal runs of flexible vent shall be supported at maximum  foot intervals; vertical runs,

five feet intervals. Metal strapping, properly secured, is an acceptable means to support
the flexible vent.

5. Flexible vent spacers are to be installed at intervals prescribed by the flexible vent manu-

facturer; and in such a way as to maintain concentric inner and outer vent spacing.

D. Attaching flexible venting to vertical termination assemblies.

1. When using Simpson pipe, an MHSC flex-to-pipe adapter (FPA) and/or rigid pipe section(s)

is required to connect the flexible vent assembly to the vertical termination by using three
self-penetrating screws.

. Review Figure 39 and corresponding instructions for proper overlap, clamp and screw

placement.

3. Three each self-penetrating screws are drilled opposite one another and below the gear

clamp.

4. Use only listed and approved terminations and accessories, installed per the installation

instructions and Figure 38.

E. Installing flexible venting to horizontal termination assemblies.
1. Connect the 5" flexible vent to the horizontal termination as in Figure 40.
. Connect the 8" flexible vent to the termination ring as in Figure 40.
3. Review Figure 40 for proper overlap and clamp placement.
4. Three each self-penetrating screws are drilled opposite one another and below the gear

lamp.

5. Use only listed an approved terminations and accessories, installed per the termination

instructions and Figure 40.

Termination
Cap

Storm Collar

Roof Support

Flashing

Rigid Pipe
Length

Flex to Pipe
Adapter
(FPA/8)

Firestop

UL1777 Flex
PIpe

DVF8A/8
Adapter

Figure 38 -
Typical Vertical Flex Vent Installation

FP1975
pipe connection

Screws
(3 Places
equidistant
just above
gear clamp)

Rigid Pipe Length

Flex to Pipe Adapter
(FPA/8)

Gear Clamp

1C\v" Flexible Pipe and Adapter
Outer Collar Overlap

UL1777 Flex Vent

Figure 39 -
Typical Pipe Connection

Gear
Clamp

FP1976
horizontal flex

Screws
(3 Places equidistant just
above gear clamp)

Gear Clamp

UL1777 Flex Vent

1C\v" Flexible Pipe and
Collar Overlap

MHSC Horizontal
Vent Termination

Figure 40 -
Typical Horizontal Flex Vent Installation

1DA 5" x 8" to 4"
x 6B\," Reducer

FP1974