Mldv series gas fireplace – Monessen Hearth DIRECT VENT MLDV500 User Manual

Page 54

Advertising
background image

54

75D0004

MLDV Series Gas Fireplace

TROUBLESHOOTING

STANDING PILOT IGNITION MILLIVOLT SYSTEM

SYMPTOM

POSSIBLE CAUSE

ACTION

4. Frequent pilot

outage problem.

5. The pilot and main

burner extinguish
while in operation

6. Glass Soots

7. Flame burn blue

and lifts off burner
(ghosting)

A. Pilot flame may be too high

or too low, causing pilot
safety to drop out

A. Inner vent pipe leaking

exhaust gases back into
system

B. Horizontal vent improperly

pitched

C. Improper vent cap installa-

tion

A. Flame impingement on logs

A. Insufficient oxygen being

supplied

A. Clean and adjust the pilot flame for maximum flame

impingement on thermocouple.

A. Check for flue product leak. Replace defective pipe sec-

tion.

B. Check horizontal-venting piping is running upward 1/4"

per foot. Do not run the pipe level or downward.

C. Check for proper installation and freedom from debris

or blockage.

A. Install log set per the instructions
Inspect the injector and air intake area. Make sure

this area does not have any blockage from debris and
clean.

Check gas supply.

A. Ensure that the vent cap is installed properly and free of

debris. Ensure that the vent system joints are tight and
have no leaks. Ensure that no debris has been blocking
the inner air intake at the bottom back of the combustion
chamber. Ensure that the glass is properly secure and
latch.