Mldv series gas fireplace, Fp1952 sidewall vent graph, Venting installation how to use the vent graph – Monessen Hearth DIRECT VENT MLDV500 User Manual

Page 15: Dimensions in feet

Advertising
background image

75D0004

15

MLDV Series Gas Fireplace

VENTING INSTALLATION

HOW TO USE THE VENT GRAPH

The Vent Graph should be read in conjunction with the following
vent installation instructions to determine the relationship between
the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe

exiting through the outer wall. Using this dimension on the
Sidewall Vent Graph below, locate the point intersecting with
the slanted graph line.

. From the point of this intersection, draw a vertical line to the

bottom of the graph.

3. Select the indicated dimension, and position the fireplace in

accordance with same.

Example: If the vertical dimension from the floor of the fireplace

is 11' (3.4 m) the horizontal run to the face of the outer wall must
not exceed 14' (4.3 m).

Example: If the vertical dimension from the floor of the unit is

7’ (2.14 m), the horizontal run to the face of the outer wall must
not exceed 7' (2.1 m).

Sidewall Vent Graph showing the relationship between vertical and
horizontal dimensions for a Direct Vent flue system.

Figure 13 -
Rear Wall Venting Graph

Horizontal dimension from the finished outside wall

to the center of the pipe on the fireplace

V

ertical Dimension From the Floor of Unit to the

Center of the Horizontal V

ent Pipe

Dimensions in

Feet

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

G =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

F =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

G

Balcony -

with no side wall

M =
Combustible &
Noncombustible
12" (305 mm)

M

Balcony -

with perpendicular side wall

M = 24" (610 mm)
P = 20” (508 mm)

M

F

Alcove Applications*

C

D

C

E

V

V

Combustible &

Noncombustible

V

V

V

E

= Min. 6” (152 mm) for

non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls

O

= 8’ (2.4 m) Min.

O

P

Figure 12 -
Allowable
Venting

584-15

No.

of Caps

D

Min.

C

Max.

1

3’ (914 mm)  x D

Actual



6’ (1.8 m)

1 x D

Actual

3

9’ (.7 m)

/3 x D

Actual

4

1’ (3.7 m)

1/ x D

Actual

D

Min.

= # of Termination caps x 3

C

Max.

= ( / # termination caps) x D

Actual

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or
non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. . All mechanical air intakes within 10’ (1 m) of a
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must
be a minimum of 1’ (305 mm) below the termination cap.