Mldv series gas fireplace, Fp1955 horizontal vent cap, Venting installation – Monessen Hearth DIRECT VENT MLDV500 User Manual

Page 17: Fp1956 vinyl siding, Fp1957 vent cap w hor pipe, Notice w arning notice

Advertising
background image

75D0004

17

MLDV Series Gas Fireplace

VENTING INSTALLATION

REAR WALL VENT INSTALLATION (continued)

HOT

FP1956

vinyl siding

Cut Vinyl Siding Away
to Fit Standoff

Standoff #150 or
5DT-VS
(Not required for
MHSC termination)

Termination

Bolt

Wood Screw

Nut

Apply Mastic
to all Four
Sides

Figure 18 -
Install Simpson/Selkirk Vinyl Siding Standoff and
Termination

FP1956

FP1957
vent cap w hor pipe

Inerior Wall
Surface

Firestop

Horizontal
Vent Pipe

Screw

Vent Cap
(Horizontal
Termination)

Figure 19 -
Install Firestop on Horizontal Vent Pipe

FP1957

NOTE: Replace the wood screws with appropriate fasteners for

stucco, brick, concrete or other types of siding.

For vinyl siding, stucco or wood exterior, use vinyl siding standoffs

between vent cap and exterior wall for Simpson or Selkirk Termina-
tions only. The vinyl siding standoff prevents excessive heat from
melting the vinyl siding material. NOTE: MHSC Termination does
not require standoff. Bolt the vent cap to the standoff or wall. Apply
non-hardening mastic around outside edge of the standoff instead
of the vent cap assembly. Use wood screws provided to attach the
standoff. Figure 18

6. Slide the stop over the vent pipe before connecting the horizontal

run to the vent cap. Figure 19

7. Carefully move the fireplace with vent assembly attached toward the

wall and insert the vent pipe into the horizontal termination. The pipe
overlap should be a minimum of 1

1

/

4

". Apply silicone to the outer pipe

connection. Fasten all vent connections with screws provided.

8. Slide the wall thimble against the interior wall surface and attach

with screws. Figure 19

HO

T

FP1955
horizontal vent cap

Vent Cap

Wood Screw

Apply Mastic to all
Four Sides

Figure 17 -
Install Horizontal Termination

Do not recess vent termination into any wall.
This will cause a fire hazard.

All rear vent through-the-wall applications
must use MHSC-designed 5 x 8 square termi-
nation. No other manufacturer's termination is
pemitted in this application.

For more information, follow instructions
provided with terminations.

NOTICE

W

ARNING

NOTICE