Mldv series gas fireplace, Venting installation, Warning – Monessen Hearth DIRECT VENT MLDV500 User Manual

Page 20

Advertising
background image

0

75D0004

MLDV Series Gas Fireplace

VENTING INSTALLATION

1. Locate and cut the vent opening in the wall. For

combustible walls first frame in opening.

Combustible Interior Walls: Cut a 1

Z\x

"H x

10

Z\x

" W hole through the interior wall.

Combustible Exterior Walls: Cut a 10

Z\x

"H

x 10

Z\x

"W square hole through the exterior

wall frame. Figure 25

Noncombustible Walls: Hole opening should

be 8

Z\x

" (16 mm) in diameter.

. The center of the hole should line up with the

center line of the horizontal rigid vent pipe end.
Allow 1/4" minimum rise per foot. Figure 25

1. Locate and cut the vent opening in the wall. For com-

bustible walls first frame in opening.

Combustible Interior Walls: Cut a 11Z\x"H x 9Z\x" W hole

through the interior wall.

Combustible Exterior Walls: Cut a 9Z\x"H x 9Z\x"W

square hole through the exterior wall frame. Figure 26

Noncombustible Walls: Hole opening should be 7Z\x"

(190 mm) in diameter.

. The center of the hole should line up with the center line

of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot. Figure 26

HORIZONTAL WITH VERTICAL RISE (THROUGH-THE-WALL) APPLICATIONS

NOTE: #1222DA reducer must be used when 4x6B\,"
venting is preferred. Reducer must be installed directly
onto unit at pipe adaptor before vertical rise.

W

ARNING

You may use a reducer from 5" x 8" to 4" x 6B\,"
for horizontal with vertical rise applications.
ONLY use framing instructions below when
using 4" x 6B\," venting.
If the reducer is installed at the rear of the
unit, you must immediately follow with a 90
elbow for a vertical rise before continuing
with any horizontal run. There is a minimum
total height of 7 feet from the fireplace floor
to the last section of pipe. Refer to graph on
Page 17.

FP1954
wall framing

10

1

/



"

(67 mm

)

10

1

/



"

(67 mm

)

8

1

/



"

(16 mm

)

Figure 25 -
Exterior Wall Framing Dimensions for 5" x 8"

Combustible

Wall

Noncombustible

Wall

FP1954

FP1954
wall framing

9

1

/



"

(41 mm

)

9

1

/



"

(41 mm

)

7

1

/



"

(190 mm

)

Combustible

Wall

Noncombustible

Wall

FP1954

Figure 26 -
Exterior Wall Framing Dimensions for 4" x 6

5

/

8

"