HORIZONTAL (THROUGH-THE-WALL) TERMI-
NATION CONFIGURATION
(continued)

If a 90° elbow is used in the horizontal vent run (level height

maintained) the horizontal vent length is reduced by 36".
Figure 23. This does not apply if the 90° elbows are used to
increase or redirect a vertical rise. Figure 22

Example: According to the vent graph (Page 17) the maximum
horizontal vent length in a system with a 7.5' vertical rise is 20’
(6 m) and if a 90° elbow is required in the horizontal vent it must
be reduced to 17' (5.2 m).
In Figures 22 and 23 dimension A plus B must not be greater
than 17' (5. m).

The maximum number of 45° elbows permitted per side wall

installation is two (). These elbows can be installed in either
the vertical or horizontal run.

For each 45° elbow installed in the horizontal run, the length

of the horizontal run MUST be reduced by 18" (457 mm).
This does not apply if the 45° elbows are installed on the
vertical part of the vent system.

The maximum number of elbow degrees in a system is 70°.

Figure 24

VENTING INSTALLATION

Figure 23 -
Maximum Vent Run with Elbows

FP1959

A + B = 17' Maximum

Horizontal 90° Elbow = 3' Reduction

7'6"

10'

7'

A

B

FP1958
Horizontal run reduction

Figure 22 -
Horizontal Run Reduction

90°

7'6"

A

B

FP1958

Example:

Elbow 1 = 90°

Elbow  = 45°

Elbow 3 = 45°

Elbow 4 = 90°

Total Angular Variation = 70°

Figure 24 -
Maximum Elbow Usage

1 +  + 3 + 4 = 70°

1
2
3
4

1
2
3
4

FP1180