L1 Controller Error Messages

007-4857-002

145

L1 Controller

Error Messages

Table 7-2 lists error messages that the L1 controller generates and displays on the L1 display. This
display is located on the front of the IRU.

Note: In Table 7-2, a voltage warning occurs when a supplied level of voltage is below or above
the nominal (normal) voltage by 10 percent. A voltage fault occurs when a supplied level is below
or above the nominal voltage by 20 percent.

Table 7-2

L1 Controller Messages

L1 System Controller Message

Message Meaning and Action Needed

Internal voltage messages:

ATTN: <power VRM description> high fault limit
reached @ x.xxV

30-second power-off sequence for the IRU.

ATTN: <power VRM description> low fault limit
reached @ x.xxV

30-second power-off sequence for the IRU.

ATTN: <power VRM description> high warning
limit reached @ x.xxV

A higher than nominal voltage condition is detected.

ATTN: <power VRM description> low warning
limit reached @ x.xxV

A lower than nominal voltage condition is detected.

ATTN: <power VRM description> level stabilized
@ x.xxV

A monitored voltage level has returned to within
acceptable limits.

Fan messages:

ATTN: FAN <fan description> fault limit reached @
xx RPM

A fan has reached its maximum RPM level. The
ambient temperature may be too high. Check to see
if a fan has failed.

ATTN: FAN <fan description> warning limit
reached @ xx RPM

A fan has increased its RPM level. Check the
ambient temperature. Check to see if the fan
stabilizes.

ATTN: FAN <fan description> stabilized @ xx
RPM

An increased fan RPM level has returned to normal.