7: Troubleshooting and Diagnostics

Temperature messages: low alt.

ATTN: <temp sensor description> advisory
temperature reached @ xxC xxF

The ambient temperature at the IRU’s air inlet has
exceeded 30

° C.

ATTN: <temp sensor description> critical
temperature reached @ xxC xxF

The ambient temperature at the IRU’s air inlet has
exceeded 35

°C.

ATTN: <temp sensor description> fault temperature
reached @ xxC xxF

The ambient temperature at the IRU’s air inlet has
exceeded 40

°C.

Temperature messages: high alt.

ATTN: <temp sensor description> advisory
temperature reached @ xxC xxF

The ambient temperature at the IRU’s air inlet has
exceeded 27

°C.

ATTN: <temp sensor description> critical
temperature reached @ xxC xxF

The ambient temperature at the IRU’s air inlet has
exceeded 31

°C.

ATTN: <temp sensor description> fault temperature
reached @ xxC xxF

The ambient temperature at the IRU’s air inlet has
exceeded 35

°C.

Temperature stable message:

ATTN: <temp sensor description> stabilized
@ xxC/xxF

The ambient temperature at the IRU’s air inlet has
returned to an acceptable level.

Power-off messages:

Auto power down in xx seconds

The L1 controller has registered a fault and is
shutting down. The message displays every five
seconds until shutdown.

IRU appears to have been powered down

The L1 controller has registered a fault and has shut
down.

Table 7-2

L1 Controller Messages (continued)

L1 System Controller Message

Message Meaning and Action Needed