Power specifications, Table a-6, Power – Intel SGI Altix 450 User Manual

Page 179

Advertising
background image

Power Specifications

007-4857-002

157

Power Specifications

Table A-6 shows the power specifications for the system.

Heat dissipation

Altix 450

29.86 kBTU/hr maximum (based on 8.75 kW)

Cooling requirement

Ambient air cooling only

Air flow: intake (front),
exhaust (rear)

Approximately 750 CFM (normal operation)

Maximum altitude

10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) non-operating

Acoustical noise level

Less than 65 dBa maximum (with doors)

Table A-6

Power Specifications

Feature

Specification

Single-phase power requirements

Voltage

Frequency

Power

200-240V (180-254 VAC min/max)

50-60 Hz

17.5 kW max per tall rack

8.75 kW max per short rack

Hold-up time

16 ms

Total harmonic distortion

Less than 10% at full load

Table A-5