Grid Connection

The Solar Inverter must be connected to

the grid with five-cores (L1, L2, L3, N, PE).

We recommend a cable cross-section of

5 x 4 mm

2

.

The Solar Inverter is connected to the

supply grid via its internal printed-circuit

board terminals.

DC1 DC2 DC3

AC wiring loom

L1, L2, L3, N, PE

Illustr.: Entry openings on the underside of the device

RS 232

Alarm relais, RS485 (in and out),

irradiation sensor with integrated

temperature measurement

USB

As an input-to-grid line protection ele-

ment, we recommend using a 3 x 25 A

automatic circuit breaker for the NT

10000. No consumers may be connected

to the supply line from the Solar Inverter

to the automatic circuit breaker. The Solar

Inverter injects in three phases via termi-

nals L1, L2, and L3. Please mind the pin

assignment. A wrong assignment may

destroy the device.