Sunway NT 10000 User Manual

Page 66

Advertising
background image

150

Error

Errors 031 to 033

Grid overvoltage

> 10 %

Errors 034 to 036

Control error

Causes

The grid voltage of the

injecting phase is too high.

The Solar Inverter monitors

the lower and upper admis-

sible grid voltage limits.

If the voltage exceeds the

upper limit by 10 % (U

max

=

253 V), the Solar Inverter

will automatically be discon-

nected from the grid after

10 minutes (in compliance

with E DIN VDE 0126-1-1).

The cable cross-section of

the AC supply line to the

Solar Inverter is insufficient.

Your PV system injects elec-

tricity into an insufficiently

rated spur line.

The self-monitoring Solar

Inverter has detected a con-

trol fault.

Remedies

The grid impedance of your grid connec-

ting point is too high.

Ask your power supply company about

the stability and design of the grid.

Check the rating of your grid connection

(power meter) or the grid injection point

to your power supply company.

Ask your power supply company about

the stability and design of the grid.

Please call the technical hotline. The

phone number is on the back of the

user manual.