3.7 Error

Display

Your Solar Inverter works fully automatically.

Should external or internal factors neverthe-

less lead to an error, an error number will be

flagged on the display. Below, you will find

a description of the error for each error

number. If three consecutive error numbers

are listed in the description, each of them

refers to an energy unit of the Solar Inverter.

E. g. for the description of errors 004 to 006,

this means:

· Error 004 refers to:

DC inlet 1 (left DC connection)

energy unit 1 (lower control circuit board)

grid phase L1

· Error 005 refers to:

DC inlet 2 (middle DC connection)

energy unit 2 (middle control circuit board)

grid phase L2

· Error 006 refers to:

DC inlet 3 (right DC connection)

energy unit 3 (upper control circuit board)

grid phase L3

Errors 001 to 003

· DC overvoltage

A maximum PV generator no-load voltage

of 850 V is admissible. All components of

the DC inlet have a sufficient safety factor. If

this limit is exceeded, the Solar Inverter will

stop the injection, and «error 001» will be

flagged, for example. That means an over-

voltage of the PV generator on inlet 1 or on

the lower energy unit.

Errors 004 to 006

· Frequency fault

The Solar Inverter continuously monitors

the applied grid frequency. Should it be

outside the range specified in E DIN VDE

0126-1-1, the Solar Inverter will stop the

injection, and «error 004» will be flagged,

for example. That means a grid frequency

error on grid phase L1 or on the lower

energy unit.