147

Error

Error 016

Grid under-

voltage 3-phase

Errors 017 to 019

AFI fault current

Causes

The grid voltage is too low.

The Solar Inverter monitors

the lower and upper admis-

sible grid voltage limits in

3-phases. If the voltage

drops below the lower limit

(U

min

= 184 V), the Solar

Inverter will automatically

switch off and will only

restart when the voltage

value rises above the lower

limit again. The shutdown

can already be triggered if

the voltage drops below the

lower limit for a short time.

The AFI fault is flagged if

fault current has penetrated

the PV system and the Solar

Inverter has subsequently

disconnected from the grid.

Remedies

Ask your power supply company about

the stability and design of the grid.

The entire PV system must be checked

for insulation faults.