113

· Connection

The PV generator is connected by means of

the externally accessible, touch-safe Tyco

Solarlok connectors included in the con-

signment. The Tyco Solarlok connectors are

designed for a cable cross-section of 4 mm

2

and have to be crimped. For further infor-

mation, please read chapter 4.2 «Tyco

Solarlok Connectors».

Please note:

All PV generator inlets are positioned in

pairs. Inlet 1 is left, inlet 2 is in the middle,

and inlet 3 is right. The upper connections

are «POSITIVE», and the lower ones are

«NEGATIVE».

Illustr.: PV generator connection via Tyco

Solarlok connectors

Important Information

· The DC voltage can reach up to 850 V.

The device may only be opened by a

qualified electrician!

· As soon as the PV generator has been

connected to the Solar Inverter by means

of the DC connectors and the PV genera-

tor has been switched on, the PV genera-

tor voltage is applied internally!

· Please note that the inlet capacitors are

still live, even after the PV generator has

been switched off or the PV generator

connector has been pulled out!

· After the AC and DC sides have been

isolated, the Solar Inverter remains live

for up to approximately five minutes!

· Therefore, wait at least five minutes for

the internal voltage to discharge. Prior to

working on the Solar Inverter, always

!

GB

BP13370_NT_10000_englisch 23.11.2005 17:40 Uhr Seite 29