Sunway NT 10000 User Manual

Page 61

Advertising
background image

Error

Errors 010 to 012

Grid under-

voltage 1-phase

Errors 013 to 015

Grid overvoltage

1-phase

Causes

Objects have been deposi-

ted on the heat sink,

obstructing the convection.

The grid voltage of the

injecting phase is too low.

The Solar Inverter monitors

the lower and upper admis-

sible grid voltage limits. If

the voltage drops below the

lower limit (U

min

= 184 V),

the Solar Inverter will auto-

matically switch off and will

only restart when the volta-

ge value rises above the

lower limit again. The shut-

down can already be trig-

gered if the voltage drops

below the lower limit for a

short time.

The grid voltage of the

injecting phase is too high.

The Solar Inverter monitors

the lower and upper admis-

sible grid voltage limits.

Remedies

Remove the objects.

Ask your power supply company about

the stability and design of the grid.

Check the rating of your grid connection

(power meter) or the grid injection

point to your power supply company.

Ask your power supply company about

the stability and design of the grid.