Error 027

· Grid overvoltage 3-phase

Your Solar Inverter is equipped with an

intrinsically safe 3-phase grid monitoring

system that complies with E DIN VDE 0126-

1-1. The voltage level of phases L1, L2, and

L3 is continuously monitored. If it rises

above the maximum admissible limit value,

the Solar Inverter will stop the injection

and only restart when the voltage value

drops below the maximum admissible

limit value.

Errors 028 to 030

· Surge fault

Your Solar Inverter continuously monitors

the quality of the AC grid. If there are high

voltage peaks in the grid, the Solar Inverter

will stop the injection and try to restart.

If such a surge impulse is detected at

energy unit 3, for example, «error 030»

will be flagged.

Errors 031 to 033

· Grid overvoltage > 10 percent

If the voltage of the injecting phase has

exceeded 253 V for more than ten minutes,

the Solar Inverter will stop the injection

and only try to restart when the grid

voltage is within the admissible range

again. The functioning method complies

with E DIN VDE 0126-1-1. If the applied

grid voltage at phase L2 is higher than

253 V for more than 10 minutes, for

example, «error 032» will be flagged.

Errors 034 to 036

· Control fault

Your Solar Inverter is equipped with a self-

monitored micro controller as a standard

feature. If a fault occurs in the control

sequence, the Solar Inverter will stop the

injection and will only restart when the

fault has been eliminated. If a fault occurs

in the control circuit board of the third

energy unit (upper energy unit), for exam-

ple, «error 036» will be flagged.