General information – Sunway NT 10000 User Manual

Page 39

Advertising
background image

Start-up (without DC main switch)

1. Connect the Tyco Solarlok connectors

to your Solar Inverter.

2. Start-up the AC side.

Shut-down (with DC main switch)

1. Disconnect the PV generator side by

opening the DC main switch.

2. Open the grid connection by isolating

(switching off) the corresponding grid

fuse.

3. After a waiting time of at least five

minutes, the Solar Inverter is deener

gised.

Shut-down (without DC main switch)

1. Interrupt the grid connection by isola-

ting (switching off) the corresponding

grid fuse. A fault will then be recorded

in the fault memory of the Solar

Inverter.

2. Pull the Tyco Solarlok connector out of

your Solar Inverter.

Never disconnect the PV generator by

pulling out the Tyco Solarlok connectors

under load! Otherwise a powerful electric

arc might damage the connectors.

The damaged connectors then have to

be replaced!

2.5 Dismantling the Solar Inverter

To dismantle the Solar Inverter, loosen the

hexagon socket screws, and move the

cover up. Make sure the Solar Inverter is

de-energised; then remove the supply

lines. The Solar Inverter may then be lifted

out of the assembly frame.

!