Model ac input fuse ac reactor dc reactor – LG C Series User Manual
Page 24
Advertising

Chapter 4
-
Basic configuration
4.2 Recommended MCCB, Earth leakage circuit breaker (ELB) and Magnetic contactor
specification
Model
MCCB/
ELB(LG)
Magnetic
Contactor
Note
CI-000-C2-1P CRS33b,
EBS333
CRC-12
CI-001-C2-1P CRS33b,
EBS333
CRC-18
CI-002-C2-1P CRS33b,
EBS333
CRC-25
CI-003-C2-1P CRS33b,
EBS333
CRC-32
4.3 Recommendable
AC/DC
Reactor
Model
AC input fuse
AC reactor
DC reactor
CI-000-C2-1P
10A
2.13mH, 5.7A
7.00mH, 5.4A
CI-001-C2-1P
20A
1.20mH, 10A
4.05mH, 9.2A
CI-002-C2-1P
30A
0.88mH, 14A
2.92mH, 13 A
CI-003-C2-1P
40A
0.56mH, 20A
1.98mH, 19 A
24