background image

Chapter 10. Advanced functions

10.2 Jog operation

Group

LED display

Parameter name

Set

value

Min/Max

range

Factory

defaults

Unit

Function
group 1

F20

Jog frequency

-

0/400 10.0

Hz

I/O group

I22

[Multi-function input
terminal P3 define]

4

0/24 2

ƒ Set the desired jog frequency in F20.
ƒ Select the terminal among the Multi-function input terminal P1 thru P5 to use for this setting.
ƒ If P3 is set for Jog operation, set I22 to 4 {Jog}.
ƒ Jog frequency can be set within the range of F21 - [Max frequency] and F22 – [Start frequency].

P1

P3

CM

FX : I20 = 0

JOG : I22=4

P3 (JOG)
Run
command(FX)

Frequency

F20



Jog operation overrides all other operations except Dwell operation. Therefore, if Jog

frequency command is entered in the middle of Multi-Step, Up-Down or 3-wire

operation, operation is executed at Jog frequency.

81