Chapter 7. Function list

Function group 1

LED

display

Parameter

name

Min/Max

range

Description

Factory

defaults

Adjustable

during run

Page

F52 [Electronic

thermal level
for continuous]

50/150
[%]

ƒ This parameter sets the amount of

current to keep the motor running
continuously.

ƒ It cannot be set higher than F51 –

[Electronic thermal level for 1 minute].

100 0

0

Standard motor having cooling fan
directly connected to the shaft

F53 [Motor

cooling

method]

0/1

1

A motor using a separate motor to
power a cooling fan.

0 0

F54 [Overload

warning level]

30/150
[%]

ƒ This parameter sets the amount of

current to issue an alarm signal at a relay or
multi-function output terminal (see I54, I55).

ƒ

The set value is the percentage of H33-

[Motor rated current].

150 0

F55 [Overload

warning time]

0/30 [sec]

ƒ This parameter issues an alarm signal

when the current greater than F54-
[Overload warning level] flows to the motor
for F55- [Overload warning time].

10 0

12-2

F56 [Overload

trip

select]

0/1

ƒ This parameter turns off the inverter

output when motor is overloaded.

1 0

F57 [Overload

trip

level]

30/200
[%]

ƒ This parameter sets the amount of

overload current.

ƒ The value is the percentage of H33-

[Motor rated current].

180 0

F58 [Overload

trip

time]

0/60 [sec]

ƒ This parameter turns off the inverter

output when the F57- [Overload trip level] of
current flows to the motor for F58- [Overload
trip time].

60 0

12-3

ƒ

This parameter stops accelerating during

acceleration, decelerating during constant
speed run and stops decelerating during
deceleration.

During

Deceleration

During
constant
speed

During
Acceleration

Bit 2

Bit 1

Bit 0

0 -

-

-

1 -

-

3

2 -

3

-

3 -

3

3

4

3

- -

5

3

-

3

6

3

3

-

F59 [Stall

prevention
select]

0/7

7

3

3

3

0 X

12-3

F60 [Stall

prevention
level]

30/150
[%]

ƒ

This parameter sets the amount of

current to activate stall prevention function
during Accel, constant or Decel run.

ƒ

The set value is the percentage of the

H33- [Motor rated current].

150 X

12-3

4): Set F50 to 1 to display this parameter