Chapter 9. Basic functions

9.5

V/F control

z Linear V/F operation

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

F22 [Base

frequency]

-

30/400

60.0

Hz

F23 [Start

frequency]

-

0/10.0

0.5

Hz

Function
group 1

F30

[V/F pattern]

0

0/2 0

ƒ Set F30 to 0 {Linear}.
ƒ This pattern maintains a linear Volts/frequency ratio from F23 - [Start frequency] to F22- [Base

frequency]. This is appropriate for constant torque applications.



F22 – [Base frequency]: Inverter outputs its rated voltage at this level. Enter the motor

nameplate frequency.



F23 – [Start frequency]: Inverter starts to output its voltage at this level.

















Run
command

Freq.

Start freq.

Base freq.

Voltage

Inverter rated

voltage

z Square V/F operation

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

Function

group 1

F30

[V/F pattern]

1

0/2 0

ƒ Set F30 to 1{Square}.
ƒ This pattern maintains squared volts/hertz ratio. Appropriate applications are fans, pumps, etc.




Freq.

Base freq.

100%

Voltage



75