Chapter 7. Function list
I/O group
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
I 0
[Jump code]
0/63
This parameter sets the code number to jump.
1
O
5-5
I 1
[Filter time
constant for
V0 input]
0/9999
This is used to adjust the analog voltage input
signal via keypad potentiometer.
10 O
I 2
[V0 input Min
voltage]
0/10
[V]
Set the minimum voltage of the V0 input.
0
O
I 3
[Frequency
corresponding
to I 2 ]
0/400
[Hz]
Set the inverter output minimum frequency at
minimum voltage of the V0 input.
0.0 O
I 4
[V0 input Max
voltage]
0/10
[V]
Set the maximum voltage of the V0 input.
10
O
I 5
[Frequency
corresponding
to I 4]
0/400
[Hz]
Set the inverter output maximum frequency at
maximum voltage of the V0 input.
60.0 O
9-2
I 6
[Filter time
constant for
V1 input]
0/9999
Set the input section’s internal filter constant
for V1 input.
10 O
I 7
[V1 input Min
voltage]
0/10
[V]
Set the minimum voltage of the V1 input.
0
O
I 8
[Frequency
corresponding
to I 7]
0/400
[Hz]
Set the inverter output minimum frequency at
minimum voltage of the V1 input.
0.0 O
I 9
[V1 input max
voltage]
0/10
[V]
Set the maximum voltage of the V1 input.
10
O
I10 [Frequency
corresponding
to I 9]
0/400
[Hz]
Set the inverter output maximum frequency at
maximum voltage of the V1 input.
60.0 O
9-3
I11 [Filter
time
constant for I
input]
0/9999
Set the input section’s internal filter constant
for I input.
10 O
I12 [I
input
minimum
current]
0/20
[mA]
Set the Minimum Current of I input.
4
O
9-4
I13 [Frequency
corresponding
to I 12]
0/400
[Hz]
Set the inverter output minimum frequency at
minimum current of I input.
0.0 O
I14
[I input max
current]
0/20
[mA]
Set the Maximum Current of I input.
20
O
I15 [Frequency
corresponding
to I 14]
0/400
[Hz]
Set the inverter output maximum frequency at
maximum current of I input.
60.0 O
0 Disabled
1
Less than half the value set in I 2/7/12
entered
I16 [Criteria
for
Analog Input
Signal loss]
0/2
2
Below the value set in I 2/7/12 entered
0 O
12-7
0
Forward run command {FX}
I20 [Multi-function
input terminal
P1 define]
1
Reverse run command {RX}
0 O
9-7
2
Emergency Stop Trip {EST}
I21 [Multi-function
input terminal
P2 define]
3
Reset when a fault occurs {RST}.
1 O
4
Jog operation command {JOG}
10-3
I22 [Multi-function
input terminal
P3 define]
5
Multi-Step frequency – Low
2 O
6
Multi-Step frequency – Mid
I23 [Multi-function
input terminal
P4 define]
0/24
7
Multi-Step frequency – High
3 O
9-6