Chapter 10. Advanced functions

z Starting DC brake

Group

LED Display

Parameter Name

Set

value

Min/Max

Range

Factory

Defaults

Unit

F12

[DC Brake start voltage]

-

0/200 50

%

Function
group 1

F13

[DC Brake start time]

-

0/60 0

sec

ƒ F12: It sets the level as a percent of H33 – [Motor rated current].
ƒ F13: Motor accelerates after DC voltage is applied for the set time.

CAUTION:
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor
overheating and damage to the motor.

Freq.

Voltage

Run
command

F13

t

F12



Setting F12 or F13 to 0 will disable Starting DC brake.



t: After F13 - [DC Brake start time], the frequency is increasing after DC voltage is

applied until the time t. In this case, DC Brake start time may be longer than the set

value.

z DC brake at a stop

Group

LED Display

Parameter Name

Set

value

Min/Max

Range

Factory

Defaults

Unit

Function
group 1

F12

[DC Brake start voltage]

-

0/200 50

%

I/O
group

I22

[Multi-function input
terminal P3 define]

11

0/24 2

ƒ F12: Set as a percent of H33 – [Motor rated current].
ƒ Select a terminal to issue a command of DC brake during stop among P1 thru P5.
ƒ If P3 terminal is set for this function, set 22 to 11 {DC brake during stop}.

Caution:

If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor
overheating and damage to the motor.

Voltage

Run
command

F12

P3

80