Chapter 7. Function list

I/O group

LED

display

Parameter

name

Min/Max

range

Description

Factory

defaults

Adjustable

during run

Page

6

3

3

-

7

3

3

3

I60 [Inverter

station
number]

1/32

ƒ This parameter is set when the inverter

uses RS485 communication.

1 O

ƒ

Select the Baud rate of the RS485

0 1200

bps

1 2400

bps

2 4800

bps

3 9600

bps

I61 [Baud

rate]

0/4

4 19200

bps

3 O

ƒ It is used when frequency command is

given via V1 and I terminal or communication
option.

0 Continuous

operation

1

Free Run stop (Coast to stop)

I62 [Drive

mode

select after
loss of
frequency
command]

0/2

2

Decel to stop

0 O

I63 [Wait

time

after loss of
frequency
command]

0.1/12
[sec]

ƒ This is the time inverter determines

whether there is the input frequency
command or not. If there is no frequency
command input during this time, inverter
starts operation via the mode selected at I62.

1.0

-

12.7



55