LG C Series User Manual

Page 65

Advertising
background image

Chapter 9. Basic functions

9.2

Multi-Step frequency setting

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

0.0 [Frequency

command] 5.0 0/400

0.0 Hz

Frq [Frq

mode]

0

0/8

0

-

St1

[Multi-Step frequency 1]

- 10.0

St2

[Multi-Step frequency 2]

- 20.0

Drive
group

St3

[Multi-Step frequency 3]

-

0/400

30.0

Hz

I22

[Multi-function input
terminal P3 define]

5

2 -

I23

[Multi-function input
terminal P4 define]

6

3 -

I24

[Multi-function input
terminal P5 define]

7

0/24

4 -

I30

[Multi-Step frequency 4]

-

30.0

I31

[Multi-Step frequency 5]

-

25.0

I32

[Multi-Step frequency 6]

-

20.0

I/O
group

I33

[Multi-Step frequency 7]

-

0/400

15.0

Hz

ƒ Select a terminal to give Multi-step frequency command among P1-P5 terminals.
ƒ If terminals P3-P5 are selected for this setting, set I22-I24 to 5-7 to give Multi-step frequency

command.

ƒ Multi-step frequency 0 is settable using Frq – [Frequency mode] and 0.0 – [Frequency command].
ƒ Multi-step frequency 1-3 are set at St1-St3 in Drive group, while Step frequency 4-7 are set at I30-

I33 in I/O group.

Step

freq

FX or RX

P5

P4

P3

0

9

- - -

1

9

- - 9

2

9

-

9

-

3

9

-

9

9

4

9

9

- -

5

9

9

-

9

6

9

9

9

-

7

9

9

9

9

Frequency

P3

P4

P5

FX

RX

Step 0

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

Step 7

Step 0

65