Chapter 9. Basic functions

9.6

Stop mode select

z Decel to stop

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

Function
group 1

F4

[Stop mode select]

0

0/2 0

ƒ Set F30 to 0 {Decel to stop}.
ƒ The inverter decelerates to 0Hz for the preset time.


Run
command

Freq.

Decel time










z DC brake to stop

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

Function
group 1

F4

[Stop mode select]

1

0/2 0

ƒ Set F30 to 1 {DC brake to stop} (See page 10-1 for more).

z Free run to stop

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

Function
group 1

F4

[Stop mode select]

2

0/2 0

ƒ Set F30 to 2 {Free run to stop}.
ƒ The inverter turns off the output frequency and voltage when the run command is OFF.


Run
command

Freq, Voltage