Chapter 9 Optional Parts

101

Chapter 9 Optional Parts

9.1 Battery

9.1.1 Capacity selection

Calculate the discharging current according to rated load capacity and then select
the battery according to the current and the battery backup time required by user.
There are various specifications of battery, we recommend that 30 12V battery cells
should be connected in series to form a battery string. The capacity of battery cell
can be 38Ah, 65Ah and 100Ah.

Note

If the battery capacity exceeds 100Ah

,the user should connect the battery of

same model and same capacity in parallel or use large capacity 2V battery to make
up the battery group.

The capacity data of battery string are listed in Table 9-2 and the capacity data are
selected according to rated load. Select the battery of 70%~100% rated capacity
according to the actual load and required backup time.

Table 9-1 Battery capacity equipped for single UPS (Ah,25℃)

UPS

capacity

20kVA 30kVA

40kVA

60kVA

Discharging

current

50A 75A

100A

150A

Backup time

Battery capacity(Ah)

15min

38 65

100

100

30min

65 65

100

150

1h

100 130

180

340

2h

150 200

340

420

3h

200 340

420

630

4h

250 340

510

680

5h

340 420

630

840

6h

340 510

680

1020

8h

420 630

840

1260