Chapter 10 Service after Sales

113

Table 10-2 Fault information of Single module UPS system

No.1

Fault description

Reason

Actions to be taken

1

Ambient over-temperature over-temperature of UPS room

Check the ventilation

2

Environment parameter 1
abnormal

Environment parameter channel 1
has alarm

Check the devices relating to the
channel

3

Environment parameter 2
abnormal

Environment parameter channel 2
has alarm

Check the devices relating to the
channel

4

Environment parameter 3
abnormal

Environment parameter channel 3
has alarm

Check the devices relating to the
channel

5

Environment parameter
abnormal

12V environment parameter
channel has alarm

Check the devices relating to the
channel

6

Rectifier input voltage
abnormal

Line-to-neutral voltage of rectifier
exceeds normal operation range

Check the input line-to-neutral voltage
amplitude of rectifier

7

Rectifier input under-
voltage

Line-to-neutral voltage of rectifier
lower than 305V, but higher than
208V

Check the input line-to-neutral voltage
amplitude of rectifier

8

Rectifier’s input voltage
frequency is abnormal

Rectifier frequency exceeds the
normal range

Check the rectifier’s input voltage
frequency

9

Input fuse blows

Rectifier input fuse blows up

Notify the service dept for repairing

10

Input transformer over
temperature

Temperature of input transformer
is too high

Check the ambient temperature and
ventilation

11

Input phase rotation
Reverse

Rectifier’s input phase rotation is
reverse

Notify the UPS service engineer, check
the wiring of rectifier input cables

12 Bypass

unsynchronized

Bypass voltage or frequency is
out of normal range and inverter
output is not synchronized with
the bypass output.

Check the bypass voltage and
frequency

13

Bypass ratings exceed the
normal range

Bypass voltage or frequency
exceeds the normal range and
the bypass will not power the load
anymore.

Check the bypass voltage and
frequency

14

Bypass over current
timeout

If the over current time exceeds
the limit, the UPS may shut down
the bypass and the inverter.

Check the load, if it is normal, then
restart the UPS

15

Shutdown due to bypass
fault

When the overload time is due in
inverter mode, if at this time the
bypass has fault, then the inverter
is shut down.

Repair the bypass and reduce the load,
and then restart the UPS. Note: Don’t
let the UPS in over load state for a long
time.