Chapter 1 Introduction

11

Capacity 20kVA

30kVA

40kVA

60kVA

Model UL33-0200L

UL33-0300L

UL33-0400L

UL33-0600L

Insulation Resistance

>2M(500VDC)

Dielectric Strength

(input to earth, output to earth)2820Vdc, leakage current lower
than 3.5mA, 1min without arc

Surge Immunity

Satisfy the class IV requirements specified by IEC60664-1, the
ability to withstand 1.2/50us+8/20us not lower than 6kV/3kA

System

Protection index

IP20

Number of battery cells

30 battery cells(12V)

Installation

Cable access mode

top/bottom cable access modes optional

2. Electrical Parameters

For designing of utility power source, air-conditioner, input and output power
distribution and cable selection, please refer to Table 1-2

Table 1-2 electrical parameters

Model

UL33-0200L UL33-0300L UL33-0400L UL33-0600L

UPS rated power

20kVA

30kVA

40kVA

60kVA

AC input

Rectifier: 380/400/415V+15%~(3¢3W), Bypass: 380/400/415V±10%(3¢4W)

Rated loss

2.40kW

3.60kW

4.37kW

5.94kW

Air intake(m

3

/hour) 500

800

1400

2200

Rectifier input

current

44A 66A 88A 132A

Bypass input current

37A

56A

74A

112A

UPS output current

37A

56A

74A

112A

Battery input current

56A

84A

112A

168A