Liebert UPS System User Manual

Page 33

Advertising
background image

Chapter 3 Electrical Assembly

27

Input power cable

Parallel power cable

Wire terminal

Fig. 3-3 Power cable connection of One branch utility source

5. Connect the Load to the U, V, W terminals of UPS output breaker Q5.

6.Connection of battery cables

The positive and negative cables of batteries are connected to the Positive and
Negative terminals of JX3 respectively.

7. Connection of Neutral cable

The neutral cable of bypass source is connected to the JX5 copper bar, that is
marked with “N/INPUT”. The neutral cable of UPS output source is connected to
copper bar JX4, that is marked with “N/OUTPUT”.

Note

The phase rotation of circuit breakers Q1, Q2, Q5 cannot be wrong and the phase
rotation is shown in Figure 3-4.