Liebert UPS System User Manual

Page 70

Advertising
background image

Chapter 5 Operation of Display Panel

64

2001-11-08

UL33-0400L

12:30:20

Inv. On

Units:

ID 1

A(B)

B(C) C(A)

221

11.8 12.3 12.5

50.2 50.1 50.1

1.41 1.40 1.41

Input Breaker Close

11£ -08 12:09

Output Breaker Open

UPS in Normal Mode

Batt. Boost Charging

11£ -08 12:09

11£ -08 12:09
11£ -08 12:09
11£ -08 12:09

Mains
Bypass

Local

System

Battery

220

221

Byp. Breaker Close

Out

Power KW

Cap. KVA

Load%
Crestor
Factor

OK

Transfer with Interupt
, Confirm

Fig. 5-40 Bypass to inverter prompt

From inverter to bypass mode with interruption:

If the bypass voltage or frequency exceeds the synchronized range and the UPS is
in inverter mode, the system must let the user to confirm and accept the power
interruption danger before pressing the inverter stop key to shutdown the output of
the inverter. The user can also cancel the shutdown operation, as shown in Fig. 5-
41. If the bypass voltage restores to normal before the user makes the confirmation,
the UPS will transfer to bypass operation mode automatically, and at the same time
the prompt window will disappear soon.

2001-11-08

UL33-0400L

12:30:20

Inv. On

Units:

ID 1

A(B)

B(C) C(A)

221

11.8 12.3 12.5

50.2 50.1 50.1

1.41 1.40 1.41

Input Breaker Close

11£ -08 12:09

Output Breaker Open

UPS in Normal Mode

Batt. Boost Charging

11£ -08 12:09

11£ -08 12:09
11£ -08 12:09
11£ -08 12:09

Mains
Bypass

Local

System

Battery

220

221

Byp. Breaker Close

Out

Power KW

Cap. KVA

Load%

Crestor
Factor

OK

This operation leads
to output shutdown,
Confirm or cancel

C

Fig. 5-41 Transfer to bypass prompt

Overload due to shutdown: The parallel operation system is in inverter mode, if the
load capacity exceeds the total capacity of the remained UPS units when shut
down one UPS unit. The UPS that is to be shut down will display a prompt window
to ask the user to confirm before shutting down, as shown in Fig.5-42. If the load is
reduced before the user makes confirmation, there will be no overload for the
remained UPS units, this UPS unit will shut down automatically, and the Prompt
window will disappear automatically, the functions of the keys in the Keypad display
window will restore to normal functions.