Chapter 9 Optional Parts

106

provided by battery manufacturer. The battery output circuit breaker should be
made separately. The method is used if the required backup time is longer than
2 hours.

l. The connection cables between battery and UPS will not be provided in

accessories. Refer to Table 3-2 in Chapter 3 to select the battery cables.

9.3 SNMP Card and the Software

UPS SNMP card UF-SNMP111 is inserted into the slot for SNMP card in the UPS.
The card enables the remote management of the UPS via network.

SNMP card is compatible with 10M/100M ether net and support the SNMP, HTTP,
TFTP, TELNET and TTY protocols. The immunity satisfies the IEC 1000-4-2.3.4
LEVER III . The conduction of radiation satisfies CISPR 22 CLASS A standard. Hot
swappable design enables quick and convenient maintenance. It can access to
network management system via MIB, and is able to monitor the UPS via IE. It is
also a part of centralized monitoring system.

9.3.1 Product structure and ports

Fig.9-5 SNMP structure

The ports and functions of SNMP card are given in Table 9-4.

Table 9-3 Ports and functions of SNMP card

Serial No.

Name

Functions

1

RJ45 port

Connect to network cables

2

Status indicator(green)

Indicate the operation states of SNMP card

3

Network indicator(yellow) Indicate the network connection and communication

status

4

SNMP card

Inserted into UPS and used for UPS connection

9.3.2 Technical features

Compatible with 10/100M either net, the SNMP card can adapt to 10M and 100M
ether net automatically and can realize the smooth connection from 10M to 100M;