Chapter 10 Service after Sales

114

No.1

Fault description

Reason

Actions to be taken

16

Battery needs to be
replaced

The battery life is reduced due to
aging, which may endanger the
normal operation of UPS. Warn
the user that the battery is
abnormal and needs to be
replaced.

Notify the service dept for replacing the
battery and set the battery model and
parameters through software.

17 No

battery

Batteries are not connected.

Check the battery and the wiring of
batteries

18

Pre-alarm for end of
battery discharging

The battery discharges to pre-
alarm point(the battery capacity
is inadequate),the system may
shut down after a few minutes

Shut down the load in time

19 battery over temperature

battery temperature is too high

Check the battery temperature and
ventilation

20 battery self-test is disabled

The battery condition for self-test
is not satisfied

Start the self test after the conditions
can meet the requirements

21

Battery is connected
reverse

Battery is connected reverse

Notify the UPS service engineer to
connect the battery again

22

Bypass phase rotation is
reverse

Bypass phase rotation is reverse Notify the UPS service engineer to

change the bypass phase rotation

23

Rectifier heatsink over
temperature

Rectifier heatsink temperature is
too high

The UPS can recover automatically.
Check the environment and ventilation

24 Rectifier fan fails

Rectifier fan is abnormal

Replace the fan in time and the UPS
can recover automatically

25 Inverter

asynchronous

Inverter is asynchronous with
bypass

Check if the bypass is normal. The fault
alarm stops automatically after the
bypass recovers normal

26

Inverter heatsink over
temperature

Inverter heatsink temperature is
too high

The UPS can recover automatically.
Check the environment and ventilation

27 Inverter fan fails

Inverter fan is abnormal

Replace the fan in time and the UPS
can recover automatically

28 Inverter

over

current

The IGBT of inverter has over
current resulting in the shut down
if inverter.

Restart the inverter, if the fault can’t be
cleared, notify the service dept for
repairing.

29

Shutdown due to low bus
voltage

DC bus voltage is too low result in
the shutdown of inverter

Check whether there is fault in rectifier
side, if no, then check whether
overload occurs. Restart after clearing
the fault.

30

Output transformer over
temperature

Output transformer temperature is
too high

Auto recovery, ambient and ventilation
of UPS should be checked.

31 Overload of single UPS

Load is too heavy

Disconnect unnecessary load and
ensure the safety.

32 Overload of system

System load is too heavy

Disconnect

unnecessary load and

ensure the safety.

33

Overload exceeds normal
time

Over load occurs in inverter
mode, transfers to bypass mode

If the load decreases after 5 minutes,
the system will back to inverter mode