Chapter 3 Electrical Assemble

26

3. Cable connection

Note

All the switches should be switched off during cable connection.

1. Feed cables

Feed cables according to the cable entry mode, with reference to Figures 2-7, 2-8,
3-1, 3-2

2. Assembling cable lugs to cables

First strip the insulation layer 20 mm from the end. Then insert the conductor into
the cable lug. Then press the cable lug against the cable till tight.

The parameters of the cable lugs are given in Table 3-3

20kVA 30kVA 40kVA 60kVA

Name

terminal

Cable

(mm

2

)

terminal

Cable

(mm

2

)

terminal

Cable

(mm

2

)

terminal

Cable

(mm

2

)

Battery

GTNR25-8

25

GTNR25-8

25

GTNR50-8

35

GTNR50-8

50

Bypass H16/24

16

H16/24

16

H35/30

25

H35/30

35

Output H16/24

16

H16/24

16

H35/30

25

H35/30

35

Input H16/24

16

H16/24

16

H35/30

25

H35/30

35

Neutral
line

GTNR25-8

25

GTNR25-8

25

GTNR50-8

35

GTNR50-8

50

Earth
cable

GTNR25-8

16

GTNR25-8

16

GTNR25-8

25

GTNR25-8

25

3. Connecting the rectifier input to utility

Connect the three phase cables of phase A1, B1 and C1 to the circuit breaker Q1

4.Connecting the bypass input to utility

Connect the three phase cables of phase A2, B2 and C2 to the circuit breaker Q2.

Note :

In single input system, jumper the respective terminals on Q1 to Q2 with a 300mm
length cable. The utility will be connected to Q1 as described in 3.