Liebert UPS System User Manual

Page 92

Advertising
background image

Chapter 7 Troubleshooting

86

No.1

Fault description

Reason

Actions to be taken

49

Transfer to bypass
due to surge

The system transfers to bypass
mode due to surge current and back
to inverter mode after load is
decreased

Avoid applying load abruptly and the UPS
can recover automatically

50

User’s wrong
operation

Wrong operation such as start the
UPS with the maintenance bypass
switched on

Operate with reference to User’s Manual

51

The actual transfer
times exceed the
permissible transfer
times per hour

Transfer times exceed the times set
by background. The system will stay
in bypass mode until next hour.

Avoid frequent overload

Table 7-2 Fault of parallel operation system

No.

Fault description

Reasons

Fault processing

1

Overload of parallel
operation system

Overload occurs and the
redundancy is not available

Disconnect the load of low priority, maintain the
power supply to important load

2

Neighbouring UPS
module requires to
transfer to bypass
mode

In parallel operation system,
some UPS module may
require to transfer to bypass
due to surge or overload,
other modules will transfer to
bypass after receiving the
signal sent by this UPS
module that requires to
transfer to bypass mode

If the parallel operation system transfers to
bypass mode, and the operation condition
enables, all the UPS modules can recover to
normal mode synchronously.

3 Load

sharing

fault

The load current of each UPS
module is noticeably
unbalanced, thus the system
loading ability is affected.

Notify the service dept for repairing

4

Parallel operation
board fails

The board is damaged.

Notify the service dept for repairing

Advertising