Liebert UPS System User Manual

Page 16

Advertising
background image

Chapter 1 Introduction

10

Capacity 20kVA

30kVA

40kVA

60kVA

Model UL33-0200L

UL33-0300L

UL33-0400L

UL33-0600L

Overload capability(inverter)

105%

< load 125% , transfer to bypass mode after 10±0.1min;

125%

< load 150% , transfer to bypass mode after 1 minute;

When load > 150%, transfer to bypass mode after 200ms

Overload capability(bypass)

135% Rated Current continuously

135%~170% for 1 minute

>170%, shutdown in 2s

1000% rated current for 20ms(a standard for selecting static
switch)

Ratio of output current peak
value to RMS value

3: 1

Transfer time(normal mode)

0(uninterrupted transfer),15ms(interrupted transfer)

Output

Transfer time(ECO mode)

15ms

System efficiency(linear load)

87%

87%

88%

89%

Efficiency in battery
mode(linear load)

92% 93% 93% 94%

Display LCD+LED

Conduction EN50091-2

Radiation EN50091-2

CLASS-A

Harmonic IEC1000-3-4

EMC/EMI

Immunity

EN 61000-4-2.3.4..6.8.9.11 Level III,

EN 61000-4-5 Level Ⅳ

MTBF(inverter) 30,000

hours

MTBF(Single UPS)

150,000 hours

MTBF(1+1 parallel operation
system)

400,000 hours

Safety CCEE

Audible noise at 2m

<60dB

<65dB

Cross current without
load(1+1)

<3A

Cross current without
load(3+1)

<4A

current unbalance rate(1+1)

<3%

System

current unbalance rate(3+1)

<4%

Advertising