Chapter 7 troubleshooting, 1 ups system troubleshooting, 2 led indicator – Liebert UPS System User Manual

Page 87

Advertising
background image

Chapter 7 Troubleshooting

81

Chapter 7 Troubleshooting

7.1 UPS system troubleshooting

The following information are only for service engineers who are trained in the
repair and troubleshooting of the UPS. The maintenance engineer must be familiar
with the UPS because the UPS is rather complicated.

7.1.1 Basics

Generally, the UPS faults happen suddenly and the UPS will be shutdown or
transfer to bypass mode. So making record is very important for maintenance.
Please observe the following contents:

The error of UPS output voltage should not exceed 2%;

The battery charging current should not exceed 6A.

Find out the reasons if the UPS displayed value differs greatly with the calculated
values. The user should be informed of the load condition before starting
troubleshooting.

7.1.2 Procedures

Status recording: Record the displayed information, the buzzer sound, states of
indicators and the states of various switches when fault occurs.

Fault types: After recording all the information, look up the fault information table
and the fault indicators, if the fault type can not be determined yet, please contact
supplier or technical support engineer.

Fault record: After identifying the fault type, please notify our service engineers for
repairing.

7.2 LED indicator

7.2.1 LED display

There are 6 LEDs used for indicate the operation status and fault. There is a fault if
the LED illuminates red.

Bypass indicator: If it turns red, that means the bypass input exceeds the normal
range;

Advertising