Liebert UPS System User Manual

Page 71

Advertising
background image

Chapter 5 Operation of Display Panel

65

2001-11-08

UL33-0400L

12:30:20

Inv. On

Units:

ID 1

A(B)

B(C) C(A)

221

11.8 12.3 12.5

50.2 50.1 50.1

1.41 1.40 1.41

Input Breaker Close

11£ -08 12:09

Output Breaker Open

UPS in Normal Mode

Batt. Boost Charging

11£ -08 12:09

11£ -08 12:09
11£ -08 12:09
11£ -08 12:09

Mains
Bypass

Local

System

Battery

220

221

Byp. Breaker Close

Out

Power KW

Cap. KVA

Load%

Crestor
Factor

OK

This operation leads
to overload, Confirm
or cancel

C

Fig. 5-42 Capacity expansion

Start UPS capacity inadequate: When the UPS is in bypass mode, if the load
capacity is larger than that of one or more than one UPS unit, the UPS that has
already been start-up will not transfer to inverter mode and prompt a window to ask
the user to confirm.

When the load is reduced to be lower than the capacity of UPS, the Prompt window
will disappear.

2001-11-08

UL33-0400L

12:30:20

Inv. On

Units:

ID 1

A(B)

B(C) C(A)

221

11.8 12.3 12.5

50.2 50.1 50.1

1.41 1.40 1.41

Input Breaker Close

11£ -08 12:09

Output Breaker Open

UPS in Normal Mode

Batt. Boost Charging

11£ -08 12:09

11£ -08 12:09
11£ -08 12:09
11£ -08 12:09

Mains
Bypass

Local

System

Battery

220

221

Byp. Breaker Close

Out

Power KW

Cap. KVA

Load%

Crestor
Factor

System overload,
Turn on More UPS

Fig. 5-43 UPS capacity inadequate

Load capacity higher than that of single module UPS system: If the UPS is in
bypass operation mode, and the load capacity exceeds the total capacity of one or
more than one UPS units, the LCD of the UPS that start first will display a Prompt
window, as shown in Fig. 5-44. Under this condition, the user must decrease the
load until the load is lower than the UPS capacity, or switch on the remained UPS
until the total capacity exceeds the load capacity, thus the system can transfer to
inverter mode and the Prompt window disappears.

Advertising