Operation

92

3.5.5 Setting Up External Communication Devices

All external communication devices, including the modem, are optional equipment. Connections to

communication ports are made by wiring cables to terminal boards. Connection points are shown on

the Control Wiring Interconnect Diagram in the Installation Manual. Contact Liebert Global Services

for assistance when attaching an external device to your UPS system.
Any terminal that accepts the standard 7-bit ASCII codes and conforms to the data link requirements

can be used to interface with the Npower UPS. If a printer is used, the terminal must support it. The

UPS does not send or receive any printer control commands.
Data link requirements are:

• Asynchronous RS-232 communication
• Terminals may be configured as DTE or DCE
• Baud Rate:

Modem 1200 or 2400
Terminal 9600 only

• Data Bits: 8
• Stop Bits: 1
• Parity: None
• Handshaking: Not required
• Full Duplex

3.6

Modes Of Operation

This section illustrates the flow of power through circuit breakers, switches, and UPS components dur-

ing various modes of operation. The same modes of operation apply to all configurations of the Liebert

Npower UPS. Highlighted (thick) lines in the diagrams indicate power flow and power availability.

3.6.1 Load on Bypass

Load on bypass, with the UPS not available, is shown in the figure below. The UPS system could be in this

mode of operation during either initial startup or UPS system shutdown and isolation for maintenance.

Figure 112Load on bypass, UPS not available

3.6.2 OK to Transfer

The OK to Transfer status message will be displayed when the bypass line and UPS system output

power are both available, their voltage, frequency, and phase synchronization are matched within

specifications, and the Static Switch Disconnects are closed (ON). An alarm message may be dis-

played to indicate Load on Bypass. If no alarm is displayed, the operating status is Load On UPS.
When the OK to Transfer message is displayed, you can perform a manual transfer of the load from

the UPS system to bypass, or a manual retransfer of the load from bypass to the UPS system. See

3.3.6 - Manual Transfer for more information.

MIMIC DISPLAY

SYS. STATUS

BATTERY

INV.

LOAD

RECT.

SS

SERV

NORM