The Sign Off Date segues to Sign Off Time and back every 5 seconds.

Figure 106System status screen, page 2

Figure 107System status screen, page 3

A brownout occurs when an Input Undervoltage condition exists for more than 5 minutes. During this

time, Input Line Fail condition is not active. To determine the brown out count, highlight BROWN

OUTS and press SELECT. Once a count is made, allow 30 minutes to re-arm the counter.
The condition for blackout occurs any time all 3 phases of the input voltage sources falls below 60% of

the rated input voltage rating. The counter starts from the time the Liebert Global Services completes

the startup procedure, and signs off the SYSTEM STATUS Screen. The counter is automatically re-

enabled when all 3 phases of the input voltage source rise above the 60% limit.
The Accumulated Number Of Blackouts (Blackout Counter) can be viewed by highlighting BLACK

OUTS and pressing SELECT.

Figure 108System status screen, page 4

STATUS DEFINITIONS AND CONDITIONS

Accumulated Installed Hours

MANUAL XFERS 0

MANUAL REXFERS 0

ALL XFERS 0

ALL REXFERS 0

SYSTEM STATUS

EXIT

NEXT

SIGN OFF DATE 10/30/01

PREV

SYSTEM STATUS

NEXT PREV SAVE & EXIT

BROWN OUTS 0

BLACK OUTS 0

BACKUP TIME 0 H 00M 00S

SIGN OFF DATE 02/15/02

OVERLOAD CONDITIONS 0

UNSUCCESSFUL AUTO REXFERS 1

AUX TEMP

AVERAGE LOAD 74%