3.3.3 Shutdown

To shut down the UPS, navigate to the MAIN MENU, and select STARTUP/SHUTDOWN. This

action will display the STARTUP/SHUTDOWN screen. From there, highlight USER SHUTDOWN

and press SELECT. The following figure will appear.

Figure 30 User shutdown screen

The Operator can invoke two types of shutdowns from this interface screen:

• Transfer Load (Inverter Off). Selecting this option transfers the load to Bypass and turns off the

Rectifier and Inverter.

• Critical Load Shutdown. Selecting this option enables a total system shutdown for purposes of

servicing or repair. The critical load will be dropped once the command is acknowledged by the

controls. Once the Operator has initiated this command, a final warning message will be issued

that “The UPS load will be dumped if you continue.” If accepted (“Continue”), the system will shut

down.

When Operator selects TRANSFER LOAD (INVERTER OFF), the MANUAL TRANSFER/

RETRANSFER screen is displayed. This allows the Operator to transfer the critical load in and out of

the static switch bypass. This screen can be accessed only when the rotary switch is in Normal posi-

tion. The screen is accessed from the MAIN MENU.

Figure 31 Manual transfer / retransfer screen when transfer is allowed

Figure 32 Manual transfer / retransfer screen when transfer is not allowed

USER SHUTDOWN

CRITICAL LOAD SHUTDOWN

EXIT

INVERTER OFF

BYPASS OK

INVERTER OK

INT. BYP. SWITCH NORMAL

EXT. MAINT. SWITCH ON-LINE

INVERTER LAG 1 DEGREE

MANUAL TRANSFER / RETRANSFER

EXIT

TRANSFER TO BYPASS

OK

MANUAL TRANSFER / RETRANSFER

BYPASS NOT OK

INVERTER OK

INTERNAL BYPASS SWITCH NORMAL

EXT. MAINT. SWITCH ON-LINE

TRANSFER NOT ALLOWED

OK

EXIT

INVERTER IN SYNC