Operation

34

The message Retransfer to UPS or Transfer to Bypass will appear depending on status of the critical

load. The operator has two choices: Either to accept OK or EXIT. If a transfer or retransfer is not

allowed, the FLASHING message Transfer Not Allowed is displayed. Press EXIT to return to the

MAIN MENU.
For more information, see 3.3.6 - Manual Transfer.

3.3.4 Status Reports

Status Reports contain sequential information about fault and alarm signals. To access the Status

Report screens, navigate to the MAIN MENU and highlight STATUS REPORTS. Press the Select

button and the following STATUS REPORTS screen is displayed

Figure 33 Status report screen

The Status Report screen is divided into six submenus: EVENT LOG, HISTORY LOG 1, HISTORY

LOG 2, SYSTEM STATUS, CLEAR HISTORY LOGS, and CLEAR EVENT LOGS.
To look at any of the reports, do the following:
1. From the Status Reports screen, press the Up or Down button to move the highlighted cursor to

the desired selection.

2. Press the Select button to view the desired report page.
To return to the Main Menu, highlight EXIT and press Select.

NOTE
The Event Log and History Log reports can be displayed on a remote terminal. For more

information see 3.5 - Communication Interfaces.

STATUS REPORTS

HISTORY LOG 1

HISTORY LOG 2

EXIT

HISTORY LOG 1

HISTORY LOG 2

SYSTEM STATUS

CLEAR HISTORY LOGS

CLEAR EVENT LOG