Operation

27

3.3.2 Startup

There are two start up scenarios which can be followed depending on whether there is already power

supplied to the UPS and the UPS is on Bypass, or there is no power to the UPS. Follow the appropri-

ate instructions.

First Scenario

Power is not supplied to the UPS (Upstream breakers are open). Locate the Rotary Switch located on

the inside of the cabinet on the lower right side as you face the cabinet. Turn the Rotary Switch to the

Normal position. For a Single Input unit close the upstream breaker so that power is applied to the

UPS. For Dual Input units close both the Input and Bypass line breakers so that power is applied to

the Input of the UPS and the Bypass line. At this time, power will be applied to the load through the

internal static bypass.

Figure 21 System ratings screen

As soon as power is applied, you will see the SYSTEM RATINGS screen (Figure 21). These are the

ratings of the unit that were programmed in at the factory. Using the arrow keys highlight SAVE &

EXIT and push the SELECT button. This will advance you to the USER SETTINGS screen. The

USER SETTINGS have been pre-set at the factory. However, they may be customized for your site.

See 3.3.5 - Configuration Screens for detail information on configuration screens. You can change

these configurations at any time. Use the arrow keys to move the cursor to SAVE & EXIT and push

SELECT. This will move you to the MIMIC screen that will look like Figure 22. You are now ready to

follow the instructions for automatic start up; see Auto Startup on page 28. Service technicians

may alternately use the Manual Start Up procedure for troubleshooting purposes in Manual

Startup on page 29.

Figure 22 Mimic display screen with load on bypass and switches closed

SYSTEM RATINGS

KVA 40

SYSTEM POWER FACTOR 0.8
INPUT VOLTS 480

OUTPUT VOLTS 208

BYPASS VOLTS 480

EXIT

NEXT

MIMIC DISPLAY

BATTERY

INV.

LOAD

RECT.

SYS STATUS

LOAD