Alarm messages, Table 7 alarms, functions, and corrective actions, Table 7 – Liebert 30-130kVA User Manual

Page 82: Alarms, functions, and corrective actions, Table 7 - alarms, Functions, and corrective actions

Advertising
background image

Operation

74

Alarm Messages

The alarm message area displays the alarm conditions that are present within the UPS system. The

table below shows the default values of masks for each alarm/fault, the meaning of the Alarm and

possible corrective actions.
The following information applies to the table.
1. Latch Masks, Dial Masks and unshaded Event log masks may be changed by the user. The user

may not change any Freeze Masks.

2. The default alarm names for Input Contact 1 through Input Contact 8 can be modified by the

user.

Table 7

Alarms, functions, and corrective actions

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)

Battery Fuse

Fail

Battery Fuse

Fail

Fault

YES

YES

NO

YES

Control Logic has determined that the

battery breaker(s) is closed and the battery

fuse has been open for 10 seconds or

longer. Battery back-up is no longer

available. Liebert Global Services should

be called immediately.

Battery Low

xfer

Battery Low

Transfer

Fault

YES

YES

YES

YES

Control Logic has determined that the

battery breaker(s) is closed and the battery

voltage has dropped below the End of

Discharge limit. The UPS will transfer to

bypass. If the transfer is successful, the

UPS will be shut down. If the transfer was

unsuccessful, logic will attempt to complete

a System Shutdown before control power is

lost. Verify that input power is now available

and restart the UPS following the

instructions in this manual. If the system

fails to restart properly contact Liebert

Global Services.

DC Ov

Transient

DC Overvolt

Transient

Fault

YES

YES

NO

YES

DC bus voltage is 15% or more over the

nominal DC Bus Voltage. The UPS will

transfer the load to Bypass and will shut

down and isolate the UPS Module. Contact

Liebert Global Services immediately

Inp Phase

Rot Error

Input Phase

Rotation Error

Fault

NO

NO

NO

YES

The power conductors on the Input line are

not wired to the UPS in the required

sequence. This alarm should appear only

during initial start-up or after a repair to the

source power system. Disconnect power

from the Input line and correct the wiring.

Liebert Global Services must be present

during initial start-up of your UPS System.

Rectifier Fuse

Fail

Rectifier Fuse

Fail

Fault

YES

YES

NO

YES

At least one fuse has opened. The UPS

automatically transfers the critical load to

the bypass line. Contactors trip open to

shut down and isolate the UPS module.

Contact Liebert Global Services

immediately. Do not attempt to reset the

circuit breakers.