Automatic module off line – Liebert 30-130kVA User Manual

Page 103

Advertising
background image

Operation

95

Automatic Module Off Line

For specified UPS system faults, the control logic will initiate an automatic transfer to bypass fol-

lowed immediately by a shutdown and isolation of the UPS system. All UPS contactors and the bat-

tery circuit breaker are opened. The static bypass switch will close if the bypass line is available. Note

that the bypass line is usually not available during Low Battery Shutdown.
The following UPS system faults will initiate an automatic transfer to bypass:

• DC Over-Voltage Shutdown
• Hardware Shutdown
• Inverter Fault
• Low-Battery Shutdown
• Output Over-Voltage
• Overload Shutdown
• Over-Temperature Time out
• Rectifier Fuse Blown
• Reverse Power

Refer to 3.4 - Faults, Alarms, Status for more information regarding these alarm messages.